Proline Promag 50W, 53W
Endress+Hauser 5
MODBUS interface:
Transmission technology (Physical Layer): RS485 in accordance with ANSI/TIA/EIA-485-A:
1998, galvanically isolated
MODBUS device type: Slave
Adress range: 1...247
Bus address adjustable via miniature switches or local display (optional) at the measuring device
Supported MODBUS function codes: 03, 04, 06, 08, 16, 23
Broadcast: supported with the function codes 06, 16, 23
Transmission mode: RTU oder ASCII
Supported baudrate: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud
Response time:
Direct data access = typically 25...50 ms
Auto-scan buffer (data range) = typically 3...5 ms
Available output combination Page 7 ff.
FOUNDATION Fieldbus interface:
FOUNDATION Fieldbus H1
Transmission technology (Physical Layer): IEC 61158-2 (MBP), galvanically isolated
ITK version 4.01
Current consumption: 12 mA
Error current FDE (Fault Disconnection Electronic): 0 mA
Bus connection with integrated reverse polarity protection
Function blocks: 5 x analog input, 1 x discrete output, 1 x PID
Output data: volume flow, calculated mass flow, temperature, totalizer 1...3
Input data: positive zero return (ON/OFF), reset totalizer
Link Master (LM) functionality is supported
Signal on alarm Current output failure response selectable (e.g. in accord. with NAMUR Recom. NE 43)
Pulse/frequency output failure response selectable
Status output (Promag 50) non-conductive by fault or power supply failure
Relay output (Promag 53) de-energized by fault or power supply failure
Load See “Output signal”
Switching output Status output (Promag 50, Promag 53):
Open collector, max. 30 V DC / 250 mA, galvanically isolated.
Configurable for: error messages, Empty Pipe Detection (EPD), flow direction, limit values.
Relay outputs (Promag 53):
Normally closed (NC or break) or normally open (NO or make) contacts available
(default: relay 1 = NO, relay 2 = NC),
max. 30 V / 0.5 A AC; 60 V / 0.1 A DC, galvanically isolated.
Configurable for: error messages, Empty Pipe Detection (EPD), flow direction, limit values, batching contacts.
Low flow cutoff Switch points for low flow cutoff are selectable
Galvanic isolation All circuits for inputs, outputs, and power supply are galvanically isolated from each other.