Memo-Graph S 5 Operation / adjusting device settings - Set-up to commissioning
Endress+Hauser 33
Signal settings -> Analogue inputs -> Analogue input x: Profibus DP sub-menu (Option
Listener / Monitor):
Settings only required if the measured values for this channel are to be acquired using the data inter-
face (and not by an analogue input).
!
Note!
This option can only be seen if the device has been ordered with the “Profibus DP Monitor” option
and has been activated under “Interfaces - Data interface - DP bus monitor”.
Signal settings -> Analogue inputs -> Analogue input x: Profibus DP sub-menu (slave
option):
!
Note!
This menu is only available if an external Profibus module is connected to the Safety Data Manager.
Before the corresponding analogue input can be set, the “external Profibus-DP slave module” data
interface must be set in the set-up under interfaces.
Set-up -> Signal settings -> Analogue inputs -> Analogue input x -> Profibus DP (Option Listener / Monitor)
Slave address Select the address of the corresponding sensor. Every sensor, “Slave”, must have its own, individual address. The measu-
red value (of the digital bus signal) is treated in the same way as conventional analogue measuring points.
! Note!
If a slave delivers several measurement data sets (“Input Index Data” for multi-parameter sensors), each channel requires
its own channel.
Input_Data index Position where the measured value information in the PROFIBUS transmitter data set begins. For one channel devices:
“000”. Please also refer to the Operating Instructions of the connected sensor.
Data type Mainly “Floating Point”. Please refer to the Operating Instructions of the connected sensor.